Draw the reactance diagram. Calculate the total fault current in the generator and motor under the fault condition and also calculate the generator and motor post-fault current.
For the system shown in the
figure. (1) Draw the reactance diagram (2) calculate the terminal voltage and
(3) If the fault occurs at bus 4 calculate the fault current.
For the network shown in
the figure. If the fault occurs on the bus two, calculate the per-unit fault
current when Xf = 0 and Xf = j0.1 and also calculate the current contribution of
generator and motor.
For the network shown in the figure. If the fault occurs on the bus three, calculate the per-unit fault current when Xf = 0 and Xf = j0.15 and also calculate the current contribution of generator and motor.
For the network shown in
the figure. If the fault occurs on the bus two, calculate the per-unit fault
current when Xf = 0 and Xf = j0.15 and also calculate the current contribution
by the generators G1 and G2.
For the network shown in
the figure. If the fault occurs in the mid of the transmission line calculate
the per-unit fault current and actual fault current.
A 50 MVA, star connected
11kV synchronous generator is connected to a 50 MVA, 11 kV/132 kV , Delta/Star transformer,
sub-transient reactance of the generator is 0.12 p.u on a 50 MVA base and the
transformer reactance is 0.1 p.u reactance on the same base. The
generator is unloaded when a symmetrical fault occurs at point A. Find the sub-transient
symmetrical fault current on both sides of the transformer.
The reactance diagram of the system shown in the figure. If a balanced three phase fault occurs at bus 2. Calculate the sub-transient current in p.u from generator 1 and in line 1-2 and bus voltages during the fault.