Wednesday, 15 February 2017

PER UNIT REPRESENTATION - PART - 10 - REACTANCE DIAGRAM - ONE PROBLEM

ONE PROBLEM - REACTANCE DIAGRAM 
PROBLEM - 01
For the system shown in the figure, draw the reactance diagram.

PER UNIT REPRESENTATION - PART - 09 - CALCULATION OF BUS VOLTAGES - TWO PROBLEMS.

PROBLEM - 01
For the system shown in the figure, calculate the bus voltage V2 and V3.
PROBLEM - 02
For the system shown in the figure, calculate the bus voltage V1 and V2.

Thursday, 9 February 2017

PER UNIT REPRESENTATION - PART - 08 - ONE PROBLEM ON CALCULATION OF GENERATOR BUS VOLTAGE

PROBLEM - 01
For the system shown in figure draw the impedance diagram and calculate the generator bus voltage.

Monday, 6 February 2017

PER UNIT REPRESENTATION - PART - 07 - PER UNIT REPRESENTATION OF SERIES AND PARALLEL LOAD IMPEDANCE

PER UNIT LOAD IMPEDANCE
(a) Series Representation of Load Impedance
(b) Parallel Representation of load Impedance
PROBLEM - 01
For the system shown in figure, draw the reactance diagram.

Wednesday, 1 February 2017

PER UNIT REPRESENTATION - PART - 06 - TWO PROBLEMS IN PER UNIT SYSTEMS

PROBLEM - 01
For the system shown in the figure, draw the reactance diagram.
PROBLEM - 02
For the system shown in the figure, draw the reactance diagram.

PRESENTATION - PART - 05 - TWO PROBLEMS IN PER UNIT SYSTEMS

PROBLEM - 01
For the system shown in the figure draw the reactance diagram.
PROBLEM - 02

For the system shown in the figure determine the generator voltage.

Tuesday, 24 January 2017

PER UNIT REPRESENTATION - PART - 04 - TWO PROBLEMS IN PER UNIT SYSTEMS

PROBLEM - 01
For the system shown in figure draw the reactance diagram.
PROBLEM - 02
For the system shown in figure draw the reactance diagram.

Wednesday, 18 January 2017

THE PER UNIT SYSTEM – PART – 03 – THREE PROBLEMS IN PER UNIT SYSTEMS

PROBLEM – 01
A 10MVA 33kV 3-phase generator has a sub-transient reactance of 15%. The generator is connected to the motors through a transmission line and transformers as shown in fig. The motors have rated of 30MVA and 50MVA at 30kV with 20% sub-transient reactance. The 3-phase transformer are rated at 110MVA, 33 kV (delta) / 100 kV (star) with leakage reactance 8%. The line has a reactance of 50 ohms. Selecting the generator rating as the base quantities in the generator circuit determine the bus quantities in other parts of the system and evaluate the corresponding p.u. values.
PROBLEM – 02
For the system shown in the figure, draw the reactance diagram.
PROBLEM – 03
Two generators at 10MVA, 13.2kV, and15MVA, 13.2KV, respectively are connected in parallel to a bus. The bus feeds two motors rated at 10MVA and 12MVA respectively. The rated voltage of motors is 12.5kV. The reactance of each generator is 15% and that of each motor is 20% on its, own rating. Assume 50MVA, 13.2kV and 15MVA, 13.2kV base and draw the reactance diagram.

Thursday, 12 January 2017

THE PER UNIT SYSTEM – PART – 02 – PER UNIT QUNATITIES IN THREE PHASE SYSTEMS

A given value of base voltage in a three-phase system is a line-to-line voltage, and a given value of base VA is the total three-phase base VA.
A per unit phase volt-ampere has the same numerical value as the corresponding per unit line volt-ampere irrespective of three-phase connection whether star or delta.

Per unit impedance referred to either side of a three-phase transformer is the same irrespective of the three-phase connections whether they are delta/star, star/star, or delta/star.

Wednesday, 11 January 2017

THE PER UNIT SYSTEM - PART - 01 - INTRODUCTION

Power transmission lines are operated at voltage levels where kV is the most convenient unit to express voltage.  Because of a large amount of power transmitted, kilowatts or megawatts and kilovolt-amperes or megavolt-amperes are the common terms.

In a large interconnected power system operating at various voltage levels and various capacity equipment. It is very easy for analyzing the network with per unit system of quantities rather than in absolute values of quantities.
DEFINITION OF PER UNIT
The numerical per unit value of any quantity is defined as the ratio of the quantity to its base expressed as a decimal. Per unit values are dimensionless.
Per unit value = 
Ratio in percent is 100 time the value of per unit.
Percent value =
Both the percent and per unit method of calculation are simplified often more informative than the use of actual amperes, ohms, and volts.
The per unit method has an advantage over the percent method because the product or two quantities expressed in per unit itself, but the product of two quantities expressed in percent must be divided by 100 to obtain the result in percent.
For example, if the base voltage of 66kV is selected, a voltage of 11kV, 33kV and 66kV would be specified as 0.17, 0.33 and 1.00 per unit respectively or 17, 33 and 100 percent.
SELECTION OF BASE VALUE
In electrical engineering there are three basic quantities are voltage, current, and impedance. Any two of them as the base quantity, the third one automatically will have a base value depending upon the other two.
In power system calculations, usually volt-amperes (S) voltage (V) are specified. Hence Sb and Vb are chosen as the base value. The base current Ib and base impedance Zb are expressed in terms of Sb and Vb.
Actual value
Base value
Per unit value
Ia = actual current
Ib=base current
Per unit current = Ia / Ib     
Va = actual voltage
Vb=base voltage
per unit voltage = Va / Vb
Za = actual impedance
Zb=base impedance
Per unit impedance = Za/Zb
Ya = actual admittance
Ya=actual admittance
Per unit admittance = Ya/Yb
SVA = actual voltamperes
Sb = base voltamperes
Per unit voltamperes = SVA / Sb