Thursday, 18 May 2017

SYMMETRICAL FAULT CALCULATIONS – PART – 09 –APPLICATION OF THEVENIN’S THEOREM & ONE PROBLEM


PROBLEM
For the network shown in the figure. If the fault occurs in the mid of the transmission line calculate the per-unit fault current and actual fault current.

Wednesday, 17 May 2017

SYMMETRICAL FAULT CALCULATIONS – PART – 08 –APPLICATION OF THEVENIN’S THEOREM & ONE PROBLEM

PROBLEM 
For the system shown in the figure.
Calculate the fault current and short circuit MVA if three-phase a balanced fault occurs at the LV and HV side of the transformer.

SYMMETRICAL FAULT CALCULATIONS – PART – 07 –APPLICATION OF THEVENIN’S THEOREM & ONE PROBLEM

PROBLEM
For the system shown in the figure.

Calculate the fault current and short circuit MVA if three-phase a balanced fault occurs at the LV and HV side of the transformer. 

Sunday, 14 May 2017

SYMMETRICAL FAULT CALCULATIONS – PART – 06 –APPLICATION OF THEVENIN’S THEOREM & ONE PROBLEM

PROBLEM
A 50 MVA, star connected 11kV synchronous generator is connected to a 50 MVA, 11 kV/132 kV , Delta/Star transformer, sub-transient reactance of the generator is 0.12 p.u on a 50 MVA base and the transformer reactance is 0.1 p.u reactance on the same base. The generator is unloaded when a symmetrical fault occurs at point A. Find the sub-transient symmetrical fault current on both sides of the transformer.

Wednesday, 10 May 2017

SYMMETRICAL FAULT CALCULATIONS – PART – 05 – CALCULATION OF FAULT CURRENT, BUS VOLTAGES AND CURRENTS & ONE PROBLEM

PROBLEM
The reactance diagram of the system shown in the figure. If a balanced three phase fault occurs at bus 2. Calculate the sub-transient current in p.u from generator 1 and in line 1-2 and bus voltages during the fault.

Sunday, 30 April 2017

SYMMETRICAL FAULT CALCULATIONS – PART – 04 – CALCULATION OF FAULT CURRENT & PROBLEM

PROBLEM
The reactance diagram of the system shown in the figure. If a balanced three phase fault occurs at bus 2 and bus 2, calculate the fault current and also find the post-fault voltages at bus 1, 2 and 3. All the bus voltage magnitudes are one and zero degrees.

Friday, 28 April 2017

SYMMETRICAL FAULT CALCULATIONS – PART – 02 – CALCULATION OF SHORT CIRCUIT kVA & ONE PROBLEM

PROBLEM – 01
A three phase transmission line operating at 10 kV and having a resistance of 1 ohms and reactance of 4 ohms is connected to the generating station bus-bars through 5 MVA step-up transformer having a reactance of 5%. The bus bars are supplied by a 10 MVA alternator having 10% reactance. 
Calculate the short-circuit kVA fed to the symmetrical fault between phases if it occurs (i) at bus one (ii) at bus two (iii) at bus three.

Thursday, 27 April 2017

SYMMETRICAL FAULT CALCULATIONS – PART – 01 – IMPORTANCE OF FAULT CALCULATIONS

AIM OF SHORT CIRCUIT STUDY
The aim of short circuit study is to determine fault current, bus voltages and line currents under the fault condition. It is also used to determine ratings of CB and Power transformers and other power systems equipment (CT and PT).
CLASSIFICATION OF FAULTS
1. Shunt fault (short circuits) – Shunt faults involve power conductor or conductors-to-ground or short circuit between conductors. Shunt faults are characterized by the increase in current and fall in voltage and frequency.
2. Series faults (open circuits) – When circuits are controlled by fuses or any device which does not open all three phases, one or two phases of the circuit may be opened while the other phases or phase is closed. Series faults are characterized by the increase in voltage and frequency and fall in current in the faulted phases.
CAUSES OF FAULTS
Lightning, heavy winds, trees falling across lines, vehicles colliding with towers or poles, line breaks, failure of insulation etc. are the causes of faults.
ILL EFFECTS OF SHORT-CIRCUIT FAULTS
Most of the faults on the power systems lead to a short-circuit condition. When such a conditions occur, a heavy current flows through the equipment, causing considerable damage to the equipment and interruptions of service to the consumers.
IMPORTANCE OF STUDYING FAULT CALCULATIONS
Fault calculations involve finding the voltage and current distribution throughout the system during the fault condition so that the protective devices may be set to detect the fault and isolate the faulty portion of the system so as to minimize the harmful effects of such contingencies.
SYMMETRICAL FAULT
The fault on the power system which gives rise to symmetrical currents (i.e. equal fault current in the lines with 1200 displacement) is called a symmetrical fault.
UNSYMMETRICAL FAULTS
Those faults on the power system which give rise to symmetrical currents (i.e. unequal fault currents in the lines with unequal displacement) are known as unsymmetrical faults. 
Generally, the fault currents are much larger than load current and, therefore, the load currents can be neglected during fault calculation.
ASSUMPTIONS ARE MADE IN FAULT CALCULATIONS
1. The emf of all the generators is assumed to be 1 per unit
2. Shunt elements in the transformer model that account for magnetizing current and core loss is neglected.
3. Shunt capacitances of the transmission lines are neglected.
4. System resistance is neglected only inductive reactance of the system is taken into account.
THEOREM USED IN FAULT CALCULATIONS
The fault calculation of the fault current can be very easily calculated by applying Thevenin’s theorem. It is only necessary to find the open circuit emf and network impedance as seen from the fault point. In most of the calculations, the open circuit emf can be assumed to be 1pu.
STEPS INVOLVING IN FAULT CALCULATIONS
1. Draw a single line diagram of the system
2. Select a common base and find out the per unit reactance of all generators, transformers, lines etc., as referred to the common base.
3. Indicate all the reactance values in the reactance diagram.
4. Find the reactance of the system as seen from the fault point.
5. Find the fault current and fault MVA in per unit values.
6. Convert the per unit values into actual values.
7. Retrace the steps in the calculation to find the current and voltage distribution throughout the network.

Monday, 24 April 2017

BUS IMPEDANCE MATRIX – PART – 10 - MUTUALLY COUPLED BRANCHES IN Z-BUS AND ONE PROBLEM

Transmission lines have the mutual coupling with other transmission lines. It is necessary to incorporate mutually coupled branches in Z-bus.
PROBLEM – For the system shown in the figure, form bus impedance matrix.