Friday, 8 September 2017

UNSYMMETRICAL FAULT CALCULATIONS – PART – 16 – SINGLE LINE TO GROUND FAULT – PROBLEM

PROBLEM
Calculate the shunt fault current and also determine the fault current when Xn = j0.15 p.u, Xn = j0.3 p.u and Xn = j0.6 p.u and also compare the results.

UNSYMMETRICAL FAULT CALCULATIONS – PART – 15 – SINGLE LINE TO GROUND FAULT – PROBLEM

PROBLEM
A 25 MVA, 11 kV three-phase generator has a direct sub-transient reactance of 0.25 pu, negative sequence reactance on 0.35 pu and zero sequence reactance of 0.1 pu. The neutral is grounded solidly grounded. Determine the fault current and the line to line voltages for sub-transient conditions when the single line to ground fault occurs on phase R. The generator operating unloaded at rated voltage.

UNSYMMETRICAL FAULT CALCULATIONS – PART – 14 – SINGLE LINE TO GROUND FAULT – PROBLEM

PROBLEM
A 25 MVA, 11 kV synchronous generator has Z1= 0.2, Z2 = 0.2 and Z0 = 0.05 p.u. A single line to ground fault occurs on the phase R of the generator. Find the fault current and line to line voltages during the fault condition. Assume that the generator neutral is solidly grounded and the generator is operating at no load and at rated voltage at the occurrence of a fault.

UNSYMMETRICAL FAULT CALCULATIONS – PART – 13 – SINGLE LINE TO GROUND FAULT CURRENT USING MATRIX MANIPULATION

POSITIVE SEQUENCE IMPEDANCE (Z1)
The impedance offered by an equipment or circuit to positive sequence current is called positive sequence impedance.
NEGATIVE SEQUENCE IMPEDANCE (Z2)
The impedance offered by an equipment or circuit to negative sequence current is called negative sequence impedance.
ZERO SEQUENCE IMPEDANCE (Z0)

The impedance offered by an equipment or circuit to zero sequence current is called zero sequence impedance.

UNSYMMETRICAL FAULT CALCULATIONS – PART – 12 PART – 12 – SINGLE LINE TO GROUND FAULT

In a balanced three phase system negative and zero sequence currents are zero.
In a three phase, four wire system the magnitude sequence current is one-third of the current in the neutral.
The neutral is not earthed the zero sequence impedance is infinity, hence the fault current is zero.
The most common type of three phase fault is the single line to ground fault (70%).
ASSUMPTIONS
1. The impedance of the fault is zero.
2. Load currents are neglected.

3. The generated e.m.f. the system is of positive sequence only.

UNSYMMETRICAL FAULT CALCULATIONS – PART – 11

DELTA-CONNECTED WINDING
In delta connected winding no zero sequence currents flow in the lines because there is no return path for these currents.
STAR-CONNECTED WITHOUT NEUTRAL WINDING
In a three-phase, a three-wire system without a neutral network, the zero sequence line currents are zero.
STAR-CONNECTED WITH NEUTRAL GROUNDED
Three phase with neutral return zero sequence currents can flow both in the phase and windings as well as in the lines.
If the neutral is solidly grounded Zn = 0.
Total zero sequence impedance from point Ground to P is equal to the Total zero sequence impedance from Neutral to P.
The voltage to neutral or voltage to ground is the same in the case of positive and negative sequence systems.
For solidly grounded system zero sequence impedance is infinity.

UNSYMMETRICAL FAULT CALCULATIONS – PART – 10 – PROBLEM

PROBLEM

A star connected load consists of three equal resistance of 1 ohms. The load is assumed to be connected to an Unsymmetrical three-phase supply, the line voltages are 220V, 385V and 400 V. Find the symmetrical three-phase current in the R phase by the symmetrical component method.

UNSYMMETRICAL FAULT CALCULATIONS – PART – 09 – PROBLEMS

PROBLEM
An unbalanced three phase network of pure resistance draws currents of 10. 10 and 14.14 amperes respectively from the R, Y and B lines of a three phase balanced supply. Find the symmetrical components of the line currents, if the load is delta connected.
PROBLEM
Prove that (i) positive sequence of the line component is equal to [(a – 1) / a ] x positive sequence of the phase voltage.

Prove that (i) negative sequence of the line component is equal to [(a^2 – 1) / a^2 ] x positive sequence of the phase voltage.

UNSYMMETRICAL FAULT CALCULATIONS – PART – 08 – PROBLEMS

PROBLEM
The line currents in R, Y and B phases are given referred to the same reference vector. Find the symmetrical components of currents.
PROBLEM
The current in the neutral to ground connection is 18 A. Calculate the zero phase sequence components in the phases.


UNSYMMETRICAL FAULT CALCULATIONS – PART – 07 - PROBLEMS

PROBLEM
A delta connected balanced resistive load is connected across an unbalanced three-phase supply shown in the figure. Current in R and Y phases are specified. Determine the symmetrical components of the current.
PROBLEM

A delta connected load is supplied from a three-phase supply. The fuse in the blue is removed and the current in the other two lines are specified. Find the symmetrical components of currents.