Monday, 25 December 2017
Friday, 22 December 2017
Thursday, 21 December 2017
Saturday, 16 December 2017
Sunday, 10 December 2017
Tuesday, 28 November 2017
Sunday, 26 November 2017
Thursday, 23 November 2017
Tuesday, 21 November 2017
Wednesday, 15 November 2017
Friday, 10 November 2017
Thursday, 2 November 2017
Wednesday, 1 November 2017
Wednesday, 11 October 2017
UNSYMMETRICAL FAULT CALCULATIONS – PART – 35 – SEQUENCE NETWORK OF TRANSFORMER
The presence of a fault at any point in a system means generally that the system is put into an unbalanced state of operation.
In unsymmetrical fault calculations, each piece of equipment will have three value of impedance offered by each sequence current.
The zero sequence network is a single-phase component and its existence is dependent upon a closed path that must be completed through reference ground.
1. For positive or negative sequence networks, the neutral of the generator is taken as the reference bus. The reason is the positive and negative sequence components represent balanced sets and hence all the neutral point must be at the same potential for positive or negative sequence currents.
2. If there is no ground return, zero sequence currents cannot flow and in the corresponding zero-sequence networks are considered an open circuit.
3. In star connected transformer if the neutral is grounded zero-sequence current can flow in the winding.
4. If the star point is ungrounded zero sequence currents cannot flow in the winding.
5. In a delta connected, there is no neutral, hence zero-sequence currents cannot flow in the line because there is no return path. However, zero-sequence currents can circulate in the legs of the delta connected winding.
6. Due to the presence of zero sequence voltages the zero-sequence currents flowing around a delta winding.
7. When the magnetizing current in a transformer is neglected, the primary ampere-turns balance the secondary ampere-turns and current can flow in the primary only if the there is a current in secondary.
8. If the neutral point of the star connection is grounded through an impedance Zn and impedance 3Zn appears in series with Z0 in the zero-sequence network.
9. The zero sequence impedance depends upon earth connection. If there is a through the circuit for earth current, zero-sequence impedance is equal to positive sequence impedance otherwise it will be infinite.
10. Positive sequence impedance = Negative sequence impedance
zero sequence impedance = Positive sequence impedance if there is a circuit for earth current (infinite, if there is no circuit for earth current)
UNSYMMETRICAL FAULT CALCULATIONS – PART – 34 – SEQUENCE NETWORK OF LOADED THREE-PHASE GENERATOR SEQUENCE NETWORKS
A single-phase equivalent circuit of power system consisting of impedances to the current of any one sequence only is called sequence network. [OR] An equivalent network for the balanced power system under an imagined operating condition such that only one sequence component of voltages and currents is present in the system.
Sequence network is composed of impedances offered to that sequence current in the system. Three sequence networks for a given power system namely
(i) Positive sequence network (ZO) – The positive sequence network for a given power system shows all the paths for the flow of positive sequence currents in the system.
(ii) Negative sequence network (Z1) – The negative sequence network for a given power system shows all the paths for the flow of negative sequence currents in the system
(iii) Zero sequence network (Z2) - The zero sequence network for a given power system shows all the paths for the flow of zero sequence currents in the system.
Each sequence network is replaced by a Thevenin’s equivalent circuit between two points i.e. each sequence network can be reduced to a single voltage and single impedance.
One point is the fault point ‘F’ and the other point is the zero potential of reference bus N.
Va1 = Vf - Z1 IR1, Va2 = -Z2 Ia2 and Va0 = -Z0 Ia0
Ia is the current flowing from the system into the fault, its components Ia1, Ia2 and Ia0.
Z1, Z2 and Z0 are the total impedance of the positive, negative and zero sequence networks up to the fault point.
For a fault on the unloaded generator with excitation voltage Eg the following will be the sequence voltage drops.
Va1 = Eg - Z1 IR1, Va2 = -Z2 Ia2 and Va0 = -Z0 Ia0
Saturday, 7 October 2017
Friday, 6 October 2017
ELECTRICAL DIAGRAMS – PART – 04 - SINGLE LINE DIAGRAM (SLD) IMPORTANCE AND APPLICATIONS
SINGLE LINE DIAGRAM
The single-line diagram is the blueprint for electrical power system analysis. It is the first step in preparing a critical response plan and to understand thoroughly familiar with the electrical distribution system layout and design.
IMPORTANCE OF SLD
1. The SLD is the roadmap for all future testing, service and maintenance activities.
2. It provides a picture of the facility at a moment in time.
3. It needs to change as your facility changes to ensure that your systems are adequately protected.
4. The SLD is making the electrical system easily understandable for any technical person inside/outside of the factory.
APPLICATIONS OF SINGLE LINE DIAGRAM
1. Short circuit calculations 2. Coordination studies
3. Load flow studies 4. Safety evaluation studies
5. Electrical safety procedures 6. Efficient maintenance
Saturday, 30 September 2017
ELECTRICAL DIAGRAMS - PART – 03 - DIFFERENCE BETWEEN BLOCK AND LAYOUT DIAGRAM
BLOCK DIAGRAM - It is a functional drawing which shows and describes the main operating principles of the equipment or devices. It consists of principle functions or parts represented by blocks and is connected through lines that show the relationship between the blocks.
LAYOUT
DIAGRAM - A drawing meant to show the physical arrangement of
the wires and the components they connect is called layout design.
ELECTRICAL DIAGRAMS PART – 02 - DIFFERENCE BETWEEN PICTORIAL AND SCHEMATIC DIAGRAM
ELECTRIC
CIRCUIT – An electrical circuit is a path through which an
electrical current flows. A closed circuit makes electrical current flow
possible. An open circuit does not allow electrical current to flow.
An
electric circuit made up of the basic elements resistance, inductance, and
capacitance in a simple arrangement such that its performance would duplicate
that of a more complicated circuit or network.
PICTORIAL
CIRCUIT DIAGRAM - A pictorial circuit diagram uses
simple images of components.
SCHEMATIC
CIRCUIT DIAGRAM - A schematic circuit diagram is used
to give a visual representation of an electrical circuit to an electrician.
Thursday, 28 September 2017
ELECTRICAL DIAGRAMS PART – 01 - DIFFERENCE BETWEEN VECTOR AND PHASOR DIAGRAM
VECTOR
- A
quantity having direction as well as magnitude, especially as determining the
position of one point in space relative to another.
VECTOR
DIAGRAM - Vector diagram shows the direction and relative magnitude
of a vector quantity by a vector arrow. Vector diagrams can be used to describe
the velocity of a moving object during its motion. Vector diagrams can be used
to represent any vector quantity. For example, acceleration, force, and
momentum.
PHASOR - A phasor is a line whose direction represents the phase angle in electrical degrees and whose length represents, the magnitude and of the electrical quantity.
PHASOR
DIAGRAM - The graphic representation of the phasors of sinusoidal quantities
taken all at the same frequency and with proper phase relationships with
respect to each other is called a phasor diagrams. The relative position of the
phasors or phase difference which is important in a.c. calculations.
Monday, 25 September 2017
UNSYMMETRICAL FAULT CALCULATIONS – PART – 32 – DOUBLE LINE TO GROUND AND LINE TO LINE FAULT - PROBLEM
A 33 kV bus bar has a three
phase fault level of 1000 MVA. The negative and zero sequence source reactances
are 2/3 and 1/3 of positive sequence reactance. The zero sequence resistance of
the source is 50 ohms. A 30 MVA, 33 / 132 kV solidly grounded delta/star
transformer having a reactance of 0.2 per unit. Is fed from 33 kV bus. Find
fault current and fault MVA at 132 kV bus for the following faults. (a) Double
line-to-ground fault and (b) Line to Line fault.
UNSYMMETRICAL FAULT CALCULATIONS – PART – 31 – THREE PHASE FAULT AND SINGLE LINE TO GROUND FAULT - PROBLEM
A 33 kV bus bar has a
three-phase fault level of 1000 MVA. The negative and zero sequence source
reactances are 2/3 and 1/3 of positive sequence reactance. The zero sequence
resistance of the source is 50 ohms. A 30 MVA, 33 / 132 kV solidly grounded
delta/star transformer having a reactance of 0.2 per unit. Is fed from 33 kV
bus. Find fault current and fault MVA at 132 kV bus for the following faults.
(a) Three phase fault and (b) Single line to ground fault.
UNSYMMETRICAL FAULT CALCULATIONS – PART – 30 – LINE-TO-LINE FAULT - PROBLEM
A 25 MVA, 11 kV,
three-phase, 50Hz generator has Z1 = j0.25 p,u., Z2 = j0.35 p,u., Z0 = j0.1
p.u. and Zn = 0.3 ohms. If a line to line fault occurs on Y and B phases.
Calculate the fault current and per phase voltages.
Sunday, 24 September 2017
UNSYMMETRICAL FAULT CALCULATIONS – PART – 29 – LINE-TO-LINE FAULT (Zn & Zf)
UNSYMMETRICAL FAULT CALCULATIONS – PART – 29 – LINE-TO-LINE FAULT (Zn & Zf)
Consider a three-phase circuit diagram of an unloaded generator, the neutral is connected through impedance Zn and fault impedance is Zf. If a line-to-line fault between Y and B phases derive the fault current and per phase voltages.
Saturday, 23 September 2017
UNSYMMETRICAL FAULT CALCULATIONS – PART – 28 – LINE-TO-LINE FAULT
Consider a three-phase
circuit diagram of an unloaded generator, if a line-to-line fault between Y and B
phases derive the fault current and per phase voltages.
UNSYMMETRICAL FAULT CALCULATIONS – PART – 27 – DOUBLE LINE-TO-GROUND FAULT - PROBLEM
Two generators A and B are
of rating 50 MVA, 11kV, three-phase and 50 Hz are connected in parallel and supply
a substation feeder.
Generator A and B positive,
negative and zero sequence impedances are Z1= j0.6 ohms, Z2 = j0.4 ohms, Z0 =
0.2 ohms and neutral impedance Zn = j0.1 ohms.
Feeder positive, negative
and zero sequence impedances are
Z1 = Z2 = (0.4 + j0.7)
ohms, Z0 = (0.7 + j3.0) ohms.
If fault involves in Y and B phases, calculate the fault current.
If fault involves in Y and B phases, calculate the fault current.
Friday, 22 September 2017
UNSYMMETRICAL FAULT CALCULATIONS – PART – 26 – DOUBLE LINE-TO-GROUND FAULT - PROBLEM
A 25 MVA, 11 kV, 50 Hz and
three-phase generator has Z1 = j0.25 p,u., Z2 = j0.35 p,u., Z0 = j0.1 p.u. and Zn
= 0.3 ohms. If a double line to ground fault occurs on Y and B phases.
Calculate the line current, fault current, line to neutral voltages and line to
line voltages during the occurrence of fault conditions.
Thursday, 21 September 2017
UNSYMMETRICAL FAULT CALCULATIONS – PART – 25 – DOUBLE LINE-TO-GROUND FAULT - PROBLEM
A 25 MVA, 11 kV, 50 Hz and
three-phase generator has Z1 = j0.25 p,u., Z2 = j0.35 p,u. and Z0 = j0.1 p.u.
If a double line to ground fault occurs on Y and B phases. Calculate the line
current, fault current, line to neutral voltages and line to line voltages during
the occurrence of fault conditions.
UNSYMMETRICAL FAULT CALCULATIONS – PART – 24 – DOUBLE LINE-TO-GROUND FAULT – PROBLEM
PROBLEM
A 25 MVA, 11 kV, 50 Hz and three-phase generator has Z1 = j0.2 p,u., Z2 =
j0.2 p,u. and Z0 = j0.05 p.u. If a double line to ground fault occurs on Y and
B phases. Calculate the line current, fault current and line to neutral
voltages during the occurrence of fault conditionsTuesday, 19 September 2017
UNSYMMETRICAL FAULT CALCULATIONS – PART – 23 – DOUBLE LINE-TO-GROUND FAULT (Zs & Zf)
An unloaded generator with a fault on phases Y and B through impedance Zf to ground. The neutral of the generator is grounded through an impedance. Assume the generator is initially under no load.
Saturday, 9 September 2017
UNSYMMETRICAL FAULT CALCULATIONS – PART – 22 – DOUBLE LINE-TO-GROUND FAULT
Consider a double
line-to-ground fault, calculate the fault current and phase voltages.
Friday, 8 September 2017
UNSYMMETRICAL FAULT CALCULATIONS - PART - 21 - SINGLE LINE TO GROUND FAULT - PROBLEM
PROBLEM
Two generators G1 and G2
are connected in parallel the rating of each generator is 25 MVA, 11kV,
three-phase, 50 Hz generator has positive sequence reactance = X1 = 20%,
negative sequence reactance = 10% and zero sequence reactance = 15%.
CASE – 01 – G1 is grounded
through 5% reactance and G2 is ungrounded
CASE – 02 – G1 is grounded
through 5% reactance G2 is grounded
CASE – 03 – G1 and G2 are
grounded through 5% reactance
Calculate the fault
current.
UNSYMMETRICAL FAULT CALCULATIONS - PART - 20 - SINGLE LINE TO GROUND FAULT - PROBLEM
PROBLEM
Two generators G1 and G2
are connected in parallel the rating of each generator is 25 MVA, 11kV,
three-phase, 50 Hz generator has positive sequence reactance = X1 = 20%,
negative sequence reactance = 10% and zero sequence reactance = 15%.
CASE – 01 – ungrounded
neutral
CASE – 02 – grounded
neutral
CASE – 03 – G1 is grounded
and G2 is ungrounded. Calculate the fault
current.
UNSYMMETRICAL FAULT CALCULATIONS – PART – 19 - SINGLE LINE TO GROUND FAULT – TWO PROBLEMS
PROBLEM – 01
A star point of a 3 kV, 3 MVA three phase synchronous generator is solidly grounded. It's positive, negative and zero sequence impedances are 2.4, 0.45 and 0.3 ohms. The generator operating unloaded sustains a resistive fault between the R phase and ground. This fault has a resistance of 1.2 ohms. Calculate the fault current and the voltage to ground of the R phase.
PROBLEM – 02
A three phase 30 MVA, 33 kV alternator having X1 = 0.18 pu and X2 = 0.12 pu and X0 = 0.10 pu, based on its rating, is connected to a 33 kV overhead line having X1 = 6.3 ohms and X2 = 6.3 ohms and X0 = 12.5 ohms per phase. A single line to ground fault occurs at the remote end of the line. The alternator neutral is solidly grounded. Calculate the fault current.
UNSYMMETRICAL FAULT CALCULATIONS – PART – 18 – SINGLE LINE TO GROUND FAULT – TWO PROBLEMS
PROBLEM – 01
A star connected alternator
with earthed neutral. A single line to ground fault occurs near the generator
terminal of phase R. The fault current is 300 A. Calculate the sequence
currents in the other phases and also calculate the if a reactance of 0.3 ohms
is connected to the neutral calculate the fault current.
PROBLEM – 02
PROBLEM – 02
A three phase 10 MVA, 13.2
kV generator with earthed neutral supplied a feeder. The sequence impedances of
generator and feeder are mentioned below. If a single line to ground fault
occurs at the far end of the feeder, calculate the fault current.
UNSYMMETRICAL FAULT CALCULATIONS – PART – 17 – SINGLE LINE TO GROUND FAULT – PROBLEM
PROBLEM
A three-phase generator
rated 25 MVA, 13.2 kV has a solidly grounded neutral. It's positive, negative
and zero sequence impedances are 30%, 40%, and 5% respectively. Resistances are
negligible.
(i) What value of reactance
must be placed in the generator neutral so that the fault current for a line to
a ground fault of zero fault impedance shall not exceed the rated line current?
(ii) What value of
resistance in the neutral will serve the same purpose?
UNSYMMETRICAL FAULT CALCULATIONS – PART – 16 – SINGLE LINE TO GROUND FAULT – PROBLEM
PROBLEM
Calculate the shunt fault
current and also determine the fault current when Xn = j0.15 p.u, Xn = j0.3 p.u
and Xn = j0.6 p.u and also compare the results.
UNSYMMETRICAL FAULT CALCULATIONS – PART – 15 – SINGLE LINE TO GROUND FAULT – PROBLEM
PROBLEM
A 25 MVA, 11 kV three-phase generator has a direct sub-transient reactance of 0.25 pu, negative sequence reactance on 0.35 pu and zero sequence reactance of 0.1 pu. The neutral is grounded solidly grounded. Determine the fault current and the line to line voltages for sub-transient conditions when the single line to ground fault occurs on phase R. The generator operating unloaded at rated voltage.
UNSYMMETRICAL FAULT CALCULATIONS – PART – 14 – SINGLE LINE TO GROUND FAULT – PROBLEM
PROBLEM
A 25 MVA, 11 kV synchronous
generator has Z1= 0.2, Z2 = 0.2 and Z0 = 0.05 p.u. A single line to ground
fault occurs on the phase R of the generator. Find the fault current and line
to line voltages during the fault condition. Assume that the generator neutral
is solidly grounded and the generator is operating at no load and at rated
voltage at the occurrence of a fault.
UNSYMMETRICAL FAULT CALCULATIONS – PART – 13 – SINGLE LINE TO GROUND FAULT CURRENT USING MATRIX MANIPULATION
POSITIVE SEQUENCE IMPEDANCE
(Z1)
The impedance offered by an
equipment or circuit to positive sequence current is called positive sequence
impedance.
NEGATIVE SEQUENCE IMPEDANCE
(Z2)
The impedance offered by an
equipment or circuit to negative sequence current is called negative sequence
impedance.
ZERO SEQUENCE IMPEDANCE
(Z0)
The impedance offered by an
equipment or circuit to zero sequence current is called zero sequence
impedance.
UNSYMMETRICAL FAULT CALCULATIONS – PART – 12 PART – 12 – SINGLE LINE TO GROUND FAULT
In a balanced three phase system negative and zero sequence currents are zero.
In a three phase, four wire system the magnitude sequence current is one-third of the current in the neutral.
The neutral is not earthed the zero sequence impedance is infinity, hence the fault current is zero.
The most common type of three phase fault is the single line to ground fault (70%).
ASSUMPTIONS
1. The impedance of the fault is zero.
2. Load currents are neglected.
3. The generated e.m.f. the system is of positive sequence only.
UNSYMMETRICAL FAULT CALCULATIONS – PART – 11
DELTA-CONNECTED WINDING
In delta connected winding
no zero sequence currents flow in the lines because there is no return path for
these currents.
STAR-CONNECTED WITHOUT
NEUTRAL WINDING
In a three-phase, a
three-wire system without a neutral network, the zero sequence line currents
are zero.
STAR-CONNECTED WITH NEUTRAL
GROUNDED
Three phase with neutral
return zero sequence currents can flow both in the phase and windings as well
as in the lines.
If the neutral is solidly
grounded Zn = 0.
Total zero sequence
impedance from point Ground to P is equal to the Total zero sequence impedance
from Neutral to P.
The voltage to neutral or
voltage to ground is the same in the case of positive and negative sequence
systems.
For solidly grounded system
zero sequence impedance is infinity.
UNSYMMETRICAL FAULT CALCULATIONS – PART – 10 – PROBLEM
PROBLEM
A star connected load
consists of three equal resistance of 1 ohms. The load is assumed to be
connected to an Unsymmetrical three-phase supply, the line voltages are 220V,
385V and 400 V. Find the symmetrical three-phase current in the R phase by the
symmetrical component method.
UNSYMMETRICAL FAULT CALCULATIONS – PART – 09 – PROBLEMS
PROBLEM
An unbalanced three phase
network of pure resistance draws currents of 10. 10 and 14.14 amperes
respectively from the R, Y and B lines of a three phase balanced supply. Find
the symmetrical components of the line currents, if the load is delta
connected.
PROBLEM
Prove that (i) positive
sequence of the line component is equal to [(a – 1) / a ] x positive sequence
of the phase voltage.
Prove that (i) negative
sequence of the line component is equal to [(a^2 – 1) / a^2 ] x positive
sequence of the phase voltage.
UNSYMMETRICAL FAULT CALCULATIONS – PART – 08 – PROBLEMS
PROBLEM
The line currents in R, Y
and B phases are given referred to the same reference vector. Find the
symmetrical components of currents.
PROBLEM
The current in the neutral
to ground connection is 18 A. Calculate the zero phase sequence components in
the phases.
UNSYMMETRICAL FAULT CALCULATIONS – PART – 07 - PROBLEMS
PROBLEM
A delta connected balanced
resistive load is connected across an unbalanced three-phase supply shown in
the figure. Current in R and Y phases are specified. Determine the symmetrical
components of the current.
PROBLEM
A delta connected load is
supplied from a three-phase supply. The fuse in the blue is removed and the
current in the other two lines are specified. Find the symmetrical components
of currents.
Friday, 21 July 2017
UNSYMMETRICAL FAULT CALCULATIONS – PART – 06 - PROBLEM - 04
PROBLEM -04
A balanced star connected
load takes 45 A from a balanced three-phase. Four-wire supply. If the fuses in
two of the lines are removed, find the symmetrical components of the currents
before and after the fuses are removed.
UNSYMMETRICAL FAULT CALCULATIONS – PART – 05 - PROBLEM - 03
PROBLEM
(a) A system of unbalanced three-phase voltages are given. Determine the three symmetrical components of the system.
(b) The positive, negative and zero sequence voltages are given. Determine the unbalanced phase voltages Va, Vb and Vc in a circuit.
UNSYMMETRICAL FAULT CALCULATIONS – PART – 04 – PROBLEM – 02
PROBLEM – 02
In a balanced three phase
four wire system on R, Y and B line under abnormal conditions are given below.
Calculate the positive, negative and zero sequence currents respectively of the
line currents.
UNSYMMETRICAL FAULT CALCULATIONS – PART – 03 – PROBLEM – 01
PROBLEM -01
A balanced star connected
load takes 9 amps from a balanced three-phase, four wire supply. Calculate the
positive, negative and zero sequence current in the system.
Monday, 10 July 2017
UNSYMMETRICAL FAULT CALCULATIONS - PART – 02 - FACTS ABOUT SEQUENCE CURRENTS
1. A balanced three-phase system consists of positive consequence components only.
2. In a balanced three-phase system the negative and zero sequence components being zero.
3. The presence of negative or zero sequence component introduces asymmetry in the three phase system.
4. The presence of negative and zero sequence currents are the indication of abnormality in the system.
5. The vector sum of the positive and negative sequence currents of an unbalanced three phase system is zero.
6. The vector sum of all sequence currents in three phase system unbalanced is equal to IRo + IYo + IBo.
7. Three phase four wire system zero sequence current is equal to one-third of the sum of current in the neutral wire.
8. The current of a single phase load drawn from a three phase system comprises equal positive, negative and zero sequence components.
9. In the unbalanced three phase system, the magnitude of negative sequence component cannot exceed that of the positive sequence component. The phase sequence should be reversed if the negative sequence components were the greater.
10. A delta-connected load has no neutral path and the line currents
to delta-connected load can contain no zero-sequence components.
Sunday, 9 July 2017
UNSYMMETRICAL FAULT CALCULATIONS – PART – 01 - INTRODUCTION TO SYMMETRICAL COMPONENTS
When the system is
unbalanced the voltages, currents and the phase impedances are in general
unequal.
Such a system can be
resolved by a symmetrical per phase technique known as the method of
symmetrical components or three-component method.
The analysis of unbalanced cases is greatly simplified by the use
of the technique of symmetrical components.
PROFILE OF FORTESCUE
Charles LeGeyt Fortescue (1876–1936) was an electrical engineer born
in York Factory (Manitoba, Canada).
Fortescue demonstrated that
any set of N unbalanced phasors — that is, any such "polyphase" signal
— could be expressed as the sum of N symmetrical sets of balanced phasors known
as symmetrical components.
This method was proposed in the year 1918.
The paper was judged to be
the most important power engineering paper in the twentieth century.
He was awarded the Franklin
Institute's 1932 Elliott Cresson Medal for his contributions to the field of
electrical engineering.
A fellowship awarded every
year by the IEEE in his name commemorates his contributions to electrical
engineering.
He was
born in York Factory (Manitoba, Canada).
FORTESCUE’S THEOREM
An unbalanced set of n
phasors may be resolved into (n-1) balanced n-phase systems of different phase
sequence on one zero-phase sequence system. A zero-phase sequence system is one
in which all phasors are of equal magnitude and angle or they are all
identical.
PHASE SEQUENCE
A phase sequence is of the
phasors is the order in which they pass through a positive maximum.
R Y B represents positive
sequence
R B Y represents negative
sequence
The direction of phasor
rotation is anticlockwise.
SYMMETRICAL COMPONENT METHOD
According to Fortescue’s
theorem, three unsymmetrical and unbalanced phasor voltages or currents of a
three-phase system can be resolved into the following components.
1. POSITIVE-SEQUENCE COMPONENTS
Positive phase sequence component
– A balanced system of three-phase currents/voltages having positive or normal
phase sequence.
Three balanced phasors, equal in magnitude and displaced from each
other by 120° same phase sequence as the original phasors (for example R-Y-B)
2. NEGATIVE-SEQUENCE COMPONENTS
Negative phase sequence
component – A balanced system of three-phase currents/voltages having negative
or opposite phase sequence.
Three balanced phasors, equal
in magnitude and displaced from each other by 120° opposite phase sequence to
the original phasors (for example R-B-Y)
3. ZERO-SEQUENCE COMPONENTS
Zero phase sequence
component – A system of three-phase currents/voltages having equal magnitude
and having zero phase displacement.
Three unbalanced phasors of a 3-phase system can be resolved into
3 balanced systems of phasors.
Three equal phasors, equal in magnitude and zero phase
displacement from each other.
The subscripts 1, 2 and 0 are generally used to indicate positive, negative and zero phase sequence.
The subscripts 1, 2 and 0 are generally used to indicate positive, negative and zero phase sequence.
Subscribe to:
Posts (Atom)