PROBLEM
A 25 MVA, 11 kV synchronous
generator has Z1= 0.2, Z2 = 0.2 and Z0 = 0.05 p.u. A single line to ground
fault occurs on the phase R of the generator. Find the fault current and line
to line voltages during the fault condition. Assume that the generator neutral
is solidly grounded and the generator is operating at no load and at rated
voltage at the occurrence of a fault.