A 25 MVA, 11 kV synchronous
generator has Z1= 0.2, Z2 = 0.2 and Z0 = 0.05 p.u. A single line to ground
fault occurs on the phase R of the generator. Find the fault current and line
to line voltages during the fault condition. Assume that the generator neutral
is solidly grounded and the generator is operating at no load and at rated
voltage at the occurrence of a fault.
A star connected load
consists of three equal resistance of 1 ohms. The load is assumed to be
connected to an Unsymmetrical three-phase supply, the line voltages are 220V,
385V and 400 V. Find the symmetrical three-phase current in the R phase by the
symmetrical component method.
An unbalanced three phase
network of pure resistance draws currents of 10. 10 and 14.14 amperes
respectively from the R, Y and B lines of a three phase balanced supply. Find
the symmetrical components of the line currents, if the load is delta
connected.
PROBLEM
Prove that (i) positive
sequence of the line component is equal to [(a – 1) / a ] x positive sequence
of the phase voltage.
Prove that (i) negative
sequence of the line component is equal to [(a^2 – 1) / a^2 ] x positive
sequence of the phase voltage.
A delta connected balanced
resistive load is connected across an unbalanced three-phase supply shown in
the figure. Current in R and Y phases are specified. Determine the symmetrical
components of the current.
PROBLEM
A delta connected load is
supplied from a three-phase supply. The fuse in the blue is removed and the
current in the other two lines are specified. Find the symmetrical components
of currents.
A balanced star connected
load takes 45 A from a balanced three-phase. Four-wire supply. If the fuses in
two of the lines are removed, find the symmetrical components of the currents
before and after the fuses are removed.