UNSYMMETRICAL FAULT CALCULATIONS – PART – 17 – SINGLE LINE TO GROUND FAULT – PROBLEM

PROBLEM
A three-phase generator rated 25 MVA, 13.2 kV has a solidly grounded neutral. It's positive, negative and zero sequence impedances are 30%, 40%, and 5% respectively. Resistances are negligible.
(i) What value of reactance must be placed in the generator neutral so that the fault current for a line to a ground fault of zero fault impedance shall not exceed the rated line current?

(ii) What value of resistance in the neutral will serve the same purpose?