A 25 MVA, 11 kV, 50 Hz and
three-phase generator has Z1 = j0.25 p,u., Z2 = j0.35 p,u., Z0 = j0.1 p.u. and Zn
= 0.3 ohms. If a double line to ground fault occurs on Y and B phases.
Calculate the line current, fault current, line to neutral voltages and line to
line voltages during the occurrence of fault conditions.
Friday, 22 September 2017
Thursday, 21 September 2017
UNSYMMETRICAL FAULT CALCULATIONS – PART – 25 – DOUBLE LINE-TO-GROUND FAULT - PROBLEM
A 25 MVA, 11 kV, 50 Hz and
three-phase generator has Z1 = j0.25 p,u., Z2 = j0.35 p,u. and Z0 = j0.1 p.u.
If a double line to ground fault occurs on Y and B phases. Calculate the line
current, fault current, line to neutral voltages and line to line voltages during
the occurrence of fault conditions.
UNSYMMETRICAL FAULT CALCULATIONS – PART – 24 – DOUBLE LINE-TO-GROUND FAULT – PROBLEM
PROBLEM
A 25 MVA, 11 kV, 50 Hz and three-phase generator has Z1 = j0.2 p,u., Z2 =
j0.2 p,u. and Z0 = j0.05 p.u. If a double line to ground fault occurs on Y and
B phases. Calculate the line current, fault current and line to neutral
voltages during the occurrence of fault conditionsTuesday, 19 September 2017
UNSYMMETRICAL FAULT CALCULATIONS – PART – 23 – DOUBLE LINE-TO-GROUND FAULT (Zs & Zf)
An unloaded generator with a fault on phases Y and B through impedance Zf to ground. The neutral of the generator is grounded through an impedance. Assume the generator is initially under no load.
Saturday, 9 September 2017
UNSYMMETRICAL FAULT CALCULATIONS – PART – 22 – DOUBLE LINE-TO-GROUND FAULT
Consider a double
line-to-ground fault, calculate the fault current and phase voltages.
Friday, 8 September 2017
UNSYMMETRICAL FAULT CALCULATIONS - PART - 21 - SINGLE LINE TO GROUND FAULT - PROBLEM
PROBLEM
Two generators G1 and G2
are connected in parallel the rating of each generator is 25 MVA, 11kV,
three-phase, 50 Hz generator has positive sequence reactance = X1 = 20%,
negative sequence reactance = 10% and zero sequence reactance = 15%.
CASE – 01 – G1 is grounded
through 5% reactance and G2 is ungrounded
CASE – 02 – G1 is grounded
through 5% reactance G2 is grounded
CASE – 03 – G1 and G2 are
grounded through 5% reactance
Calculate the fault
current.
UNSYMMETRICAL FAULT CALCULATIONS - PART - 20 - SINGLE LINE TO GROUND FAULT - PROBLEM
PROBLEM
Two generators G1 and G2
are connected in parallel the rating of each generator is 25 MVA, 11kV,
three-phase, 50 Hz generator has positive sequence reactance = X1 = 20%,
negative sequence reactance = 10% and zero sequence reactance = 15%.
CASE – 01 – ungrounded
neutral
CASE – 02 – grounded
neutral
CASE – 03 – G1 is grounded
and G2 is ungrounded. Calculate the fault
current.
UNSYMMETRICAL FAULT CALCULATIONS – PART – 19 - SINGLE LINE TO GROUND FAULT – TWO PROBLEMS
PROBLEM – 01
A star point of a 3 kV, 3 MVA three phase synchronous generator is solidly grounded. It's positive, negative and zero sequence impedances are 2.4, 0.45 and 0.3 ohms. The generator operating unloaded sustains a resistive fault between the R phase and ground. This fault has a resistance of 1.2 ohms. Calculate the fault current and the voltage to ground of the R phase.
PROBLEM – 02
A three phase 30 MVA, 33 kV alternator having X1 = 0.18 pu and X2 = 0.12 pu and X0 = 0.10 pu, based on its rating, is connected to a 33 kV overhead line having X1 = 6.3 ohms and X2 = 6.3 ohms and X0 = 12.5 ohms per phase. A single line to ground fault occurs at the remote end of the line. The alternator neutral is solidly grounded. Calculate the fault current.
UNSYMMETRICAL FAULT CALCULATIONS – PART – 18 – SINGLE LINE TO GROUND FAULT – TWO PROBLEMS
PROBLEM – 01
A star connected alternator
with earthed neutral. A single line to ground fault occurs near the generator
terminal of phase R. The fault current is 300 A. Calculate the sequence
currents in the other phases and also calculate the if a reactance of 0.3 ohms
is connected to the neutral calculate the fault current.
PROBLEM – 02
PROBLEM – 02
A three phase 10 MVA, 13.2
kV generator with earthed neutral supplied a feeder. The sequence impedances of
generator and feeder are mentioned below. If a single line to ground fault
occurs at the far end of the feeder, calculate the fault current.
UNSYMMETRICAL FAULT CALCULATIONS – PART – 17 – SINGLE LINE TO GROUND FAULT – PROBLEM
PROBLEM
A three-phase generator
rated 25 MVA, 13.2 kV has a solidly grounded neutral. It's positive, negative
and zero sequence impedances are 30%, 40%, and 5% respectively. Resistances are
negligible.
(i) What value of reactance
must be placed in the generator neutral so that the fault current for a line to
a ground fault of zero fault impedance shall not exceed the rated line current?
(ii) What value of
resistance in the neutral will serve the same purpose?